How to Specify an Outdoor GRP Cabinet: Size, Depth, IP Rating and Base
An outdoor distribution or feeder-pillar cabinet is a small part of any electrical or communication project, but a wrong specification is expensive to fix once the cabinet is cast into a pavement. This checklist walks through the decisions in the order an installer actually meets them, using the dimensions of our FGI range as the example.
1. Start from the equipment, not the box
List what goes inside — breakers, meters, terminal blocks, a router or a controller — and add space for cable bending and future additions. FGI cabinets come in five DIN widths, from about 478 mm (DIN 00) to 1417 mm (DIN 3), and three heights: 840, 1100 and 1250 mm. A model code such as 1100/1/470 reads as height / DIN size / deep version.
2. Choose the depth
The standard depth is 338 mm. Deep versions (marked 470) are 478 mm deep and are the safer choice for bulky equipment, meter concentrations or cabinets that will be upgraded later. The extra 140 mm usually costs far less than replacing a cabinet that turned out to be too shallow.
3. Match the protection class to the site
Cabinet bodies are moulded from glass-fibre reinforced polyester (SMC), which does not rust and needs no painting. The standard rating is IP55. Where water ingress from below is a risk — low-lying ground, irrigation areas, coastal sites — specify a gasketed gland plate for IP65.
4. Plan for sun and weather
In a Mediterranean climate UV exposure is the main ageing factor for any outdoor enclosure. An optional Poly Guard X coating adds UV protection and helps the cabinet keep its colour and surface for longer.
5. Decide how the cabinet will stand
A matching plinth is the quickest option: FGI plinths are available in heights of 333, 514 and 900 mm for each DIN size and depth. For a permanent installation on a concrete foundation, steel frames for concrete casting anchor the cabinet precisely and keep it level.
6. Fit-out and accessories
Mounting plates in steel, wood or GRP, full width or split into left and right panels.
1 to 4 meter windows for outdoor metering concentration.
A fan or filter (125×125, IP55) where equipment generates heat.
Locks: half-cylinder (including utility standards), locking handle or padlock pin.
Quick checklist
Equipment list and spare capacity defined
DIN size and height selected
Standard (338 mm) or deep (478 mm) version
IP55 or IP65 with gasketed gland plate
Poly Guard X UV coating — yes or no
Plinth height or concrete casting frame
Mounting plate, meter windows, ventilation and lock type
Have the list ready? Add the catalogue numbers to your quote list on our product pages, or send us the project details through the quote form — we will get back to you within one business day.